Specifications
Timing Actions: Dual-adjustable or fixed recycle timer.
Time Ranges: Seconds, minutes, hours or days. See PDF spec sheet for more info.
Delay Adjustment: 2 x 10KΩ potentiometer controls (customer supplied), also available with fixed delay (no controls required).
Timing Accuracy: ±1% ±50msec @ 25ºC, ±5% ±50msec @ -20ºC to +55ºC.
Repeatability: ±0.5% at constant ambient temperature.
Input Voltage Range: 85% to 110% of rated voltage, 85% to 125% of rated voltage for 12VDC units.
Load Current: 12VDC to 48VDC Models: 0.5A resistive or inductive. 120VDC, 120VAC and 240VAC Models: 0.2A resistive or inductive.
Temperature Range: -20ºC to +55ºC operating, -40ºC to +85ºC storage.
Dimensions (typical): 1.6" x 0.8" x 0.225".
Leads: 22 ga. solid tinned copper, 0.2" spacing.